|
|
|
||||||||||||||
|
|
||||||||||
|
PARTIAL DISCHARGE ANALYSIS
CASE STUDY 1 PD trending is the key factor in identifying severe insulation problems and increased likelihood of stator insulation failure. PDA testing was performed on two 6.9 kV, 7000 HP induction motors of the same age and design. |
||||||||||
|
||||||||||
|
Trending graph of +NQN and -NQN values of motor B. |
Visual inspection verifies the insulation failure |
|||||||||
|
CASE STUDY 2 Using PDA monitoring to extend the lifetime of a generator with severe stator winding insulation damage. During a start-up in 1993, a 730 MW, 20 kV steam turbine generator was extremely overheated due to a failure of the automatic hydrogen cooling system. The stator winding temperature reached 165 C° before the cooling failure was discovered and the generator was immediately shut down. The wedges, filler blocks and bracing ties of both the stator and rotor were melted or burned black beyond repair. The class B thermoplastic stator insulation, however, did not fail. The opinion of many experts at the time was that, if restarted, the stator winding would most likely fail and should be rewound immediately. The confidence to continue running the generator was lost. A PDA system from ADWEL International was installed in 1993. The first on-line PDA readings were taken in July 1993, as shown in the following figure <2>. The PD levels were not alarmingly high. This suggested that the insulation system was still in good shape, even though the generator had been overheated. The utility then had confidence to continue running the generator.
CASE STUDY 3 Maximize the lifetime of rotating machines. A 13.2 kV, 13,000 HP motor operating in a petrochemical plant was tested. The insulation of the motor is epoxy mica. The first PDA test was carried out in 1993. There was high PD activity in phase C, as shown in the following figure. The predominance of negative pulses indicates that partial discharges and de-lamination were occurring at the interface of the copper conductor and the ground-wall insulation. This type of partial discharge attacks both the ground-wall insulation and turn-to-turn insulation, causing electrical treeing and turn-to-turn shorts. There is no practical means of repairing such defects. Regular PDA monitoring can detect any progress in PD activity and give an indication of further insulation deterioration and increased likelihood of failure.
CASE STUDY 4 Higher sensitivity of 500 pF capacitors gives better PD detection than 80 pF capacitors. A 6.9 kV, 6000 HP motor was tested under the same operation conditions to compare the detection sensitivity of the 80 pF capacitor and the 500 pF capacitor.
The 80 pF capacitor detected almost no partial discharges, while the 500 pF capacitor detected a number of partial discharges on the same motor. Higher sensitivity capacitors bring the following benefits:
|
||||||||||